24kV VCB
24kV VCB
24kV VCB

ZW32-24 Outdoor Vacuum Circuit Breaker

ZW32-24
ZW32-24 outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short circuit protection in 24kV, 50Hz/60Hz power system.
Quantity
Contact Now
add to cart
ZW32-24 Outdoor Vacuum Circuit Breaker
ZW32-24 outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short circuit protection in 24kV, 50Hz/60Hz power system.
It is applicable for substations, industry and mining, urban and rural electricity power networks, especially applicable in occasions with frequent operation and automatic
power distribution network. It accords with the standard of IEC62271-100 & GB1984 AC high voltage circuit breaker, GB/T11022 HV general technical requirement of switch
and control apparatus.
 
Technical Parameter
 
ItemUnitData
Rated voltagekV24
Rated frequencyHz50
Rated currentA630
Rated short circuit breaking currentkA16/20
Rated short circuit making current (peak)
kA40/50
Rated short-duration withstand current (4s)kA16/20
Rated withstand current (peak)
kA40/50
Mechanical lifeTimesSpring Operation 10000/Permanent Magnetic 30000
Rated operating sequence
O-0.3s-CO-180s-CO
Breaking number for rated short-circuit current
Times30
Power frequency withstand voltage (1min)kV
65/79
Lightning impulse withstand voltage (peak)kV
95
Closing timems25~60
Total breaking timems≤100
Arcing timems≤20
Rated input power of energy storage motorW40
Rated operating voltage and auxiliary circuit rated voltage
V

DC220/110/24 AC220/110

Motor energy storage time
s≤8
Secondary circuit power frequency withstand voltage (1min)
V2000
 
ItemClosing coilOpening coilOver-current tripping coil
Rated voltage (V)220220
Rated working current(A)

AC:5 DC:3.2

AC:5 DC:0.8

5
Voltage and current rang under normal workingAction on 65%-110% of rated voltageAction on 65%-110% of rated voltage avoid tripping under less than 30% of rated voltageAction on 65%-110% of rated voltage avoid tripping under less than 90% of rated voltage
 
 
 
 
 
 
 
 
 
 
Outline and installation dimensions
 
Why Us?
1. Schneider trusted material supplier, you no worry for quality control;
2. STL standard testing lab inside own property factory industrial zone; 
3. 23 years experience of production Medium voltage circuit breaker material, 17 years for overseas market; you no worry for communication and save time.