CT19BN(W)

CT19BN(W) Spring Operating Mechanism

CT19BN(W)
CT19BN(W) spring operating mechanism is an improvement on CT19 spring operating mechanism, has much better stability and reliability.
Quantity
Contact Now
add to cart
CT19BN(W) Spring Operating Mechanism
CT19BN(W) spring operating mechanism is an improvement on CT19 spring operating mechanism, has much better stability and reliability.
CT19BW spring operating mechanism will be used in 35kV (ZW7) outdoor pole mounting vacuum circuit breaker and other vacuum circuit breaker with equivalent closing power,
CT19BN spring operating mechanism will be used in 35kV (ZN23) vacuum circuit breaker and other vacuum circuit breaker with equivalent closing power, its performances can meet
requirements of GB1984 AC High Voltage Circuit Breaker and the product's Technical Conditions; all technical parameters meet or exceed IEC standard.
 
Two kinds of closing power energy-storages: motor or manual energy-storage; Three kinds of break-brake operations: break-brake electromagnet, over-current trip electromagnet and manual button;
Two kinds of closing operations: closing electromagnet, manual button.
 
Technical Parameter
 
1.The technical parameters of the mechanism and main components:
Item
Weight (KG)
High*Width*Deep(mm)
Motor input power (W)
Closing spring (mm)
Matched vacuum circuit breaker opening current (kA)
CT19BN40440*360*160250Φ1031.5
CT19BW45550*360*160250Φ10+Φ631.5

2.Closing/Opening electromagnet adopt solenoid electromagnet, technical parameter as Table:

Rated operate voltage (V)

AC110AC220DC110 CloseDC110 OpenDC220 CloseDC220 Open

Rated operating current(A)

4.33.82.341.162

Rated power (W)

<437<836<253<440<255<440

Coil resistance at 20°C (Ω)

8.5±0.519.2±1.247±2.827.5±1.7190±5106±3

Normal operating voltage range

Open at 65%~120% rated operate voltage; do not open when less than 30% rated operate voltage

Close at 85%~110% rated operate voltage; do not close when less than 30% rated operate voltage

3.Mechanism output angle 50-55 degree.

4.The combination and code of release: 104、114、1114、1134、400

Outline and installation dimensions

Why Us?
1. Schneider trusted material supplier, you no worry for quality control;
2. STL standard testing lab inside own property factory industrial zone; 
3. 23 years experience of production Medium voltage circuit breaker material, 17 years for overseas market; you no worry for communication and save time.