Home /News&Vedio /Production Management-VCB&Operating Mechanism /Indoor 12kV Vacuum Circuit Breaker finished product testing item /
Indoor 12kV Vacuum Circuit Breaker finished product testing item
2024-12-27
What’s indoor 12kV VCB (Vacuum Circuit Breaker) fixed type finished product test item?
1. Appearance (make-up painting);
2. Primary circuit (medium voltage 12kV) resistance;
2.1. The normal value of the fixed VCB 630A primary circuit resistance is 30+—5μΩ;
2.2. VCB draw-able type, 630A, the normal value of primary circuit resistance is 40+—5μΩ, because there are more contact arm and its plum contacts
Function: It can check whether the screws in the primary circuit are tightened, and whether the model of accessories is used correctly;
3. Secondary circuit (low voltage 0.4kV 0.22kV) operating characteristics:
3.1 The operating mechanism (spring motor drive) normally open and close, check the secondary wiring, energy storage charging, opening and closing;
3.2 When 85-100% of rated voltage, is required to be able to close;
3.3 When 65-100% of rated voltage, is required to be able to open;
3.4 When less 30% of rated voltage, requires that the switch cannot be opened and closed;
4. Secondary circuit (low voltage 0.4kV 0.22kV) withstand voltage: Pass 2500V to the secondary circuit,
Function: It can check whether the secondary circuit is broken and short-circuited with other components;
5. Power frequency withstanding voltage:
5.1 VCB-12kV power frequency withstand voltage phase is 42KV relatively;
5.2 VCB-17.5KV power frequency withstand voltage phase is 50KV relatively
5.3 VCB-24KV power frequency withstand voltage phase is 65KV relatively.
17.5KV Vacuum Circuit Breaker Testing
Vacuum Interrupter First Testing its Operation for 200 Cycles in VCB