ZW32-40.5 Outdoor Vacuum Circuit Breaker
ZW32-40.5
ZW32-40.5 outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short circuit protection in 40.5kV, 50Hz/60Hz power system.
Quantity
ZW32-40.5 Outdoor Vacuum Circuit Breaker
ZW32-40.5 outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short circuit protection in 40.5kV, 50Hz/60Hz power system.
It is applicable for substations, industry and mining, urban and rural electricity power networks, especially applicable in occasions with frequent operation and automatic
power distribution network. It accords with the standard of IEC62271-100 & GB1984 AC high voltage circuit breaker, GB/T11022 HV general technical requirement of
switch and control apparatus.
Technical Parameter
| Item | Unit | Data |
| Rated voltage | kV | 36/40.5 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | 630/1250/1600/2000/2500 |
| Rated short circuit breaking current | kA | 25/31.5/40 |
Rated short circuit making current (peak) | kA | 63/80 |
| Rated short-duration withstand current (4s) | kA | 25/31.5/40 |
Rated withstand current (peak) | kA | 63/80 |
| Mechanical life | Times | Spring Operation 10000 |
Rated operation sequence | 0-0.1s-CO-3s-CO-6s-CO-60s-restore | |
Breaking number for rated short-circuit current | Times | 30 |
| Power frequency withstand voltage (1min) | kV | 95/118 |
| Lightning impulse withstand voltage (peak) | kV | 185/215 |
Secondary circuit power frequency withstand voltage | kV | 2 |
Mechanism control voltage | V | AC/DC220 |
Outline and installation dimensions