VS1-12
VS1-12
Vacuum Circuit Breaker
Vacuum Circuit Breaker

VS1-12 Indoor Vacuum Circuit Breaker

VS1-12
VS1-12 medium voltage vacuum circuit breaker is a kind of indoor medium voltage switch equipment with 50Hz/60Hz three phase AC 12kV rated voltage.
Quantity
Contact Now
add to cart
VS1-12 Indoor Vacuum Circuit Breaker
VS1-12 medium voltage vacuum circuit breaker is a kind of indoor medium voltage switch equipment with 50Hz/60Hz three phase AC 12kV rated voltage,
which combined the technology of the ABB corporation in Switzerland and developed in China.
Product complies with the standard GB1984 & IEC62271-100.
 
VS1-12 VCB usually mounted into switchgear panel KYN28 and XGN. It is applicable in occasions with frequent operation, has functions of high-speed recloser,
Multiple Opening/Closing, reliable mechanical interlock. It has fixed type & withdrawable type.
 
It adopts the composite insulated material, there is no pollution and explosion danger, the insulation level is high.
 
Technical Parameter
 
ItemUnitData
Rated voltagekV
10
Maximum working voltagekV12
Rated currentA6306301250
12501250 16001600 2000
Rated short circuit breaking currentkA202531 . 5
Rated short circuit making current (peak)kA506380
Rated withstand current (peak)kA506380
Rated short-duration withstand current (4s)
kA202531 . 5
Rated insulation level
Rated short-duration power frequency withstand voltage  (1 min)
KV42( fracture 48)
Rated lightning impulse withstand voltage (peak)75( fracture 85)
Rated operating sequenceO-0. 3s-CO-180s-CO
Mechanical lifeTimes
Spring Operation 10000
Permanent Magnetic 30000
Breaking number for rated short-circuit current
Times50
Rated operating voltage for closing coils (DC/AC)
V110,220
Rated operating voltage for opening coils (DC/AC)
V110,220
Clearance between open contacts
mm11±1
Contacting travel
mm4±0.5
Three phase opening and closing bouncing time
ms≤2
Contact closing bouncing time
ms≤2
Average opening speed
m/s0.9 ~1.2
Average closing speed
m/s0.5 ~0.8
Opening time
Under maximum operating voltage
s≤ 0.05
Under minimum operating voltage
≤ 0.08
Closing time
s≤0.1
Main circuit resistance of each phase
μΩ630≤50 1250≤40
Permissible wearing accumulated depth for movable and fixed contact
mm3
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Why Us?
1. Schneider trusted material supplier, you no worry for quality control;
2. STL standard testing lab inside own property factory industrial zone; 
3. 23 years experience of production Medium voltage circuit breaker material, 17 years for overseas market; you no worry for communication and save time.