CTB Spring Operating Mechanism
CTB
CTB spring operating mechanism will be used in ZW32-12 outdoor high voltage vacuum circuit breaker (designed by Beijing Electrical Science Academy) and outdoor or indoor vacuum circuit breaker with equivalent closing power.
Quantity
CTB Spring Operating Mechanism
CTB spring operating mechanism will be used in ZW32-12 outdoor high voltage vacuum circuit breaker (designed by Beijing Electrical Science Academy) and
outdoor or indoor vacuum circuit breaker with equivalent closing power, its performances can meet requirements of GB1984 AC High Voltage Circuit Breaker
and the product's Technical Conditions.
CTB-S manual operating mechanism holds functions of manual energy-storage; manual closing/opening; overcurrent protection.
CTB-D motor operating mechanism functions including motor or manual energy-storage; electromagnet or manual closing/opening; overcurrent
protection. To realize overcurrent protection, the controller holds functions of surge current, time delay and fast breaking.
Technical Parameter
1.Energy storage motor adopt unidirectional permanent DC motor, technical parameter as Table:
Item | ZYJ220-53-216 | ZYJ110-53-216 | ZYJ48-53-216 | ZYJ24-53-216 |
Rated operate voltage (V) | DC220 | DC110 | DC48 | DC24 |
Rated power (W) | 40 | 40 | 40 | 40 |
Normal operating voltage range | 85%-110% | 85%-110% | 85%-110% | 85%-110% |
Rated operating current(A) | 0.5 | 1.0 | 1.8 | 4.6 |
Motor energy storage time (S) | ≤8 | ≤8 | ≤8 | ≤8 |
2.Closing/Opening electromagnet adopt solenoid electromagnet, technical parameter as Table:
Rated operate voltage (V) | AC220 | AC110 | DC200 | DC110 | DC48 | DC24 |
Rated operating current(A) | 1.36 | 3.6 | 2 | 5.3 | 10 | 20 |
Rated power (W) | <300 | <396 | <440 | <583 | <480 | <480 |
Coil resistance at 20°C (Ω) | 54 | 10.3 | 106 | 20.5 | 4.8 | 1.2 |
Normal operating voltage range | Open at 65%~120% rated operate voltage; do not open when less than 30% rated operate voltage | |||||
Close at 85%~110% rated operate voltage; do not close when less than 30% rated operate voltage | ||||||
3.Manual energy storage is operated by the handle allocated with the mechanism, the operating force less than 100 (N.m)
4.Mechanism output angle 40 degree.
Outline and installation dimensions

Why Us?
1. Schneider trusted material supplier, you no worry for quality control;
2. STL standard testing lab inside own property factory industrial zone;
2. STL standard testing lab inside own property factory industrial zone;
3. 23 years experience of production Medium voltage circuit breaker material, 17 years for overseas market; you no worry for communication and save time.