Power frequency testing for 24kV Vacuum Circuit Breaker
2023-06-27
Power frequency testing for 24kV Vacuum Circuit Breaker
Phase to phase, phase to earth power frequency withstand voltage; IEC standard required 65kV;
Left first meter is the power frequency withstand voltage kV;
Second meter is the leakage current A;
Third meter is timer;
Requires withstand voltage time of 60s not break down, If it fails, the voltage cannot be maintained to 60s, the equipment will trip, and it cannot be re-setting input 65kV voltage.
The leakage current is only less than 2A, the testing equipment & VCB is about 1A; there is a protection relay inside, if the leakage current exceeds 2A, it will be opened to protect the power frequency withstand voltage test equipment;
The leakage current VS1 (Indoor type VCB) is only 0.5A; the outdoor VCB is larger such as ZW32 has 1A, and the others are the leakage current of the testing equipment;
The leakage current is the creaking sound zzzzzzzzz, during the power frequency withstand voltage test;
The leakage current of VS1 is small, and the creaking sound can hardly be heard.
The leakage current of the outdoor VCB power frequency withstanding voltage creaking sound is obvious.
Why the testing room always kept dark?
Electric sparks can be seen in the dark if there is an electrical discharge
Indoor 12kV Vacuum Circuit Breaker finished product testing item